UPS2000-G Series
High Reliability
• 5kA lightning protection design on input port
• 80-280 Vac wide input voltage range to minimize battery use: 280-176 Vac
for 100% load; 176-80 Vac for 100%-40% load (derating linearly)
• Failure alarm in advance for key components including bus capacitors, fans,
and batteries
Low TCO
• High efficiency: up to 95% for 15/20 kVA; 94.5% for 10 kVA; 94% for 6
kVA
• High power density of up to 20kVA/3U
High Availability
• Highly expandable design: up to 4 units paralleled together
• Flexible battery configuration
• Rack/tower convertible
Intelligent Battery Management
• Intelligent temperature compensation
• Intelligent hibernation technology extending battery lifespan
• Battery capacity estimation and health evaluation using self-learning
technology
Easy Management
• User friendly Liquid Crystal Display(LCD) that displays operation states in
real time
• Various communication interfaces including RS485, USB, dry contacts and
SNMP
• Web access using SSL
OTHERS | |
Height×Width×Depth (mm) | 130×430×685 |
Weight | 32 kg |
OUTPUT | |
Output wiring | Single-phase input: Ph+N+PE; Three-phase input: Ph+N+PE/3Ph+N+PE |
Rated Frequency | Tracking the bypass input (Online Mode); 50/60±0.1Hz (Battery Mode) |
Rated Voltage | L-N: 220/230/240 Vac±1% |
Waveform | Sine wave, THDv<2% |
Efficiency | 95% |
Overload Capacity | 125% overload for 5min 150% overload for 1min |
INPUT | |
Mains Input | Input Wiring Ph+N+PE /3Ph+N+PE Rated Voltage L-N: 220/230/240 Va Input Voltage Range L-N: 80-280 Vac Input Frequency Range 40-70 Hz Input Power Factor 0.99 |
Bypass | Rated Voltage L-N: 220/230/240 Vac Frequency 50/60±6 Hz |
Battery | Rated Voltage ±(192-240) Vdc |
ENVIRONMENTAL | |
Operating Temperature | 0-40 ºC |
Storage Temperature | -40-70 ºC |
Relative Humidity | 0%-95% (No condensing) |
Maximum Operating Altitude | 1000 m. Above 1000 m, derating according to IEC62040-3 |
Audible Noise | <58dB |
Communications | RS485, USB, SNMP, dry contacts |