• UPS2000-G-3K

PS2000-G Series


High Reliability

• 5kA lightning protection design on input port

• 80-280 Vac wide input voltage range to minimize battery use: 280-176 Vac

for 100% load; 176-80 Vac for 100%-40% load (derating linearly)

• Failure alarm in advance for key components including bus capacitors, fans,

and batteries

Low TCO

• High efficiency: up to 95% for 15/20 kVA; 94.5% for 10 kVA; 94% for 6

kVA

• High power density of up to 20kVA/3U



High Availability

• Highly expandable design: up to 4 units paralleled together

• Flexible battery configuration

• Rack/tower convertible


Intelligent Battery Management

• Intelligent temperature compensation

• Intelligent hibernation technology extending battery lifespan

• Battery capacity estimation and health evaluation using self-learning

technology


Easy Management

• User friendly Liquid Crystal Display(LCD) that displays operation states in

real time

• Various communication interfaces including RS485, USB, dry contacts and

SNMP

• Web access using SSL

OTHERS
Height×Width×Depth (mm) 86×440×500
Weight 8.2 kg
OUTPUT
Output wiring Ph+N+PE
Rated Frequency Tracking the bypass input (Online Mode); 50/60±0.1Hz (Battery Mode)
Rated Voltage 220/230/240 Vac±2%
Waveform Sine wave, THDv<3%
Efficiency 88%
Overload Capacity 130% overload for 60s; 150% overload for 30s
INPUT
Mains Input Input Wiring Ph+N+PE Rated Voltage 220/230/240 Vac Input Voltage Range 125-275 Vac Input Frequency Range 45-66 Hz Input Power Factor 0.95
Bypass Rated Voltage 220/230/240 Vac Frequency 50/60±6 Hz
Battery Rated Voltage 96 Vdc
ENVIRONMENTAL
Operating Temperature 0-40 ºC
Storage Temperature -20-55 ºC
Relative Humidity 0%-95% (No condensing)
Maximum Operating Altitude 1000 m. Above 1000 m, derating according to IEC62040-3
Audible Noise <45dB
Communications RS232, dry contacts

Write a review

Note: HTML is not translated!
    Bad           Good

UPS2000-G-3K

  • Brand: Huawei
  • Product Code: UPS2000-G-3K
  • Availability: In Stock
  • IQD0

  • Ex Tax: IQD0